Resumen:
A fault ride through (FRT) capability of synchronous generators is currently required by most grid codes, beyond what is required by International Electrotechnical Commission (IEC) and Institute of Electrical and Electronics Engineering (IEEE) standards for round rotor generators. This article reviews and compares FRT as required by European grid codes, and the European Network of Transmission System Operators for Electricity (ENTSO-E) grid code proposal. It investigates whether a typical round rotor turbogenerator fulfils the FRT requirements. The response of power plant auxiliaries is also analyzed. Recommendations to improve the formulation of FRT requirements are made based on thorough sensitivity studies of the response of such turbogenerators with respect to a number of variables and parameters.
Palabras Clave: Grid codes; Synchronous generators; Fault ride through capability; Transient stability; Reactive power capability; Auxiliaries
Índice de impacto JCR y cuartil WoS: 2,688 - Q2 (2016); 3,300 - Q2 (2023)
Referencia DOI: https://doi.org/10.1016/j.epsr.2016.06.046
Publicado en papel: Noviembre 2016.
Publicado on-line: Julio 2016.
Cita:
L. Díez Maroto, L. Rouco, F. Fernández-Bernal, Fault ride through capability of round rotor synchronous generators: review, analysis and discussion of European grid code requirements. Electric Power Systems Research. Vol. 140, pp. 27 - 36, Noviembre 2016. [Online: Julio 2016]